Rendered to:

BEKAERT SPECIALTY FILMS, LLC 4540 Viewridge Avenue
San Diego, California 92123

Sample ID.: Armorcoat 4 mil Clear
Size Classification: Unlimited
Lab Temperature: 71oF
Duration of Pre-Conditioning @ 65 - 85oF: 48 Hours Test Size: 34" wide by 76" high

ReportNo: 65031.01-122-37

Architectural Testing

IMPACT TESTING ON SAFETY GLAZING MATERIAL

page1image5312

1/4" Annealed Glass with Film Backing

All test specimens were destroyed by test or by our personnel and have been disposed of as trash. Impact Tests: (ANSI Class B/ CPSC Cat. I)

Test Date: Report Date: Revision 1:

10/12/06 11/10/10 03/21/07

page1image9168

Spec. Test
No. Standard

  1. 1  ANSI Z97.1-2004

  2. 2  ANSI Z97.1-2004

  3. 3  ANSI Z97.1-2004

  4. 4  ANSI Z97.1-2004

  5. 5  CSPC 16 CFR 1201

Thickness, Impact Observations Results inches Drop Height,

inches
0.231 18 No penetration after impact PASS

0.230 18 No penetration after impact PASS 0.232 18 No penetration after impact PASS

  1. 0.231  18 No penetration after impact PASS

  2. 0.232  18 No penetration after impact PASS

page1image14968 page1image15128

Conclusion: Meets the impact and weathering requirements only of the referenced standards.
Note: Weathering test results (3000 hours of Xenon-Arc exposure: ASTM G155) can be found in ATI Report No.

65031.10-122-37.

For ARCHITECTURAL TESTING, INC.:

page1image17824 page1image17984

Benjamin M. Eveler Technician I

BME:bme/nlb

Scott T. Swaltek, P.E. Senior Project Engineer

130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

page1image21072

Rev. #

0 1

Date Page(s)

11/10/10 N/A 03/21/07 One

Original report issue
Added weathering data reference to report

Architectural Testing

Revision Log Revision(s)

65031.01-122-37 Page 2 of 2 Revision 1: 03/21/07